返回首页

乐清市安航电器有限公司


直流电网绝缘监测仪

image.png

技术参数Technical parameters 

u  监测直流电网的绝缘电阻。

Monitoring the insulation resistance at the DC network system .

u  当电网绝缘电阻低于设定值时,延时1≤秒输出一报警信号;When the power grid insulation resistance is lower than the set value, delay 1 second and output an alarm signal.

u  网络工作电压Network working voltage: 24VDC100VDC220VDC

u  工作电压容差Operating voltage tolerance: ±20%

u  指示精度 Accuracy of indication:⑩(或按弧长Or arc length:±1.5%)。

u  环境温度 Ambient temperature range-25 to +55℃。

u  外壳防护 Housing protectionIP44

u  耐振动 Vibration resistance2-100HZ0.7g

u  耐电压 Dielectric testAC2.6KV50HZ1min

u  输出触点容量 Contact ratingAC250V3ADC28V3A

u  电源功耗 Power consumption:≤2VA

安装方式:面板嵌入式,垂直(⊥)安装 Panel embedded, vertical () installation. 

产品分类 Kind of products

型号

Type

展开角

angle

外形尺寸(mm

OutlineAXBXC

开孔尺寸

Cut-outmm

结构代码

Structure   code

外形图

Outline   drawing

接线图

Wiring   drawing

重量(Kg

Weight

AH110C45C9

240°

110X110X76

Figure 1

A

Figure 1

Figure  2

0.75

 规格表 Measuring range

测量范围

Measuring   range

中心值

Central   value

报警设定值

Alarm   setting value(±20%)

电压规格

Voltage   specification

备注

Note

0-0.2-5MΩ

0.2MΩ

0.01M

0.03M

0.06M

0.1MΩ

0.2MΩ

0.3MΩ

0.5MΩ

1MΩ

DC24V(DC220V)

常规routine

外形图 Outline drawing 

image.png

背部图/接线图 Back figure/Wiring diagram 

1.jpg

使用说明书Directions for use

u  仪表正确连接后,接通电源到额定电压,此时绿色指示灯亮,仪表即处于监测状态,指针指示值即为电网绝缘电阻值(自检档除外)。After the instrument is   correctly connected, connect the power supply to the rated voltage, and the   green indicator light will be on at this time, the instrument will be in the   monitoring state, and the indicator value is the insulation resistance value of   the power grid (excluding the self check file).

u  仪表在工作时报警设定开关应设置在所选定的报警值位置,具体报警值档位见背面展示图。用户有其他要求时可在订货时注明。When the instrument is working,   the alarm setting switch shall be set at the selected alarm value position.   See the back display diagram for the specific alarm value position. Other   requirements of users can be noted when ordering.

u  如需判别仪表工作是否正常时可进行自检,将仪表后面开关设置在自检档位,仪表即进行自检,仪表能进行正常自检时指针应指示在10KΩ位置,同时报警红灯点亮,报警输出端有输出。自检完毕后必须将仪表恢复到正常报警档位上。If it is necessary to judge   whether the instrument works normally, self inspection can be carried out.   Set the switch at the back of the instrument to the self inspection gear, and   the instrument will carry out self inspection. When the instrument can carry   out normal self inspection, the pointer shall indicate the position of 10KΩ, and the alarm red light will be on, and the alarm output terminal   has output. After the self-test, the instrument must be restored to the   normal alarm gear.



相关产品

下一篇:没有了!
Copyright © 2022 乐清市安航电器有限公司 备案号:浙ICP备2022035661号-1