技术参数Technical parameters 

监测直流电网的绝缘电阻。

Monitoring the insulation resistance at the DC network system .

当电网绝缘电阻低于设定值时,延时≤1秒输出一报警信号;When the power grid insulation resistance is lower than the set value, delay ≤1 second and output an alarm signal.

网络工作电压Network working voltage: 24VDC,100VDC,220VDC。

工作电压容差Operating voltage tolerance: ±20%。

指示精度 Accuracy of indication:⑩(或按弧张Or arc length:±1.5%)。

环境温度 Ambient temperature range:-25℃ to +55℃。

外壳防护 Housing protection:IP44。

耐振动 Vibration resistance:2-100HZ≤0.7g。

耐电压 Dielectric test:AC2.6KV,50HZ,1min。

输出触点容量 Contact rating:AC250V,3A;DC28V,3A。

电源功耗 Power consumption:≤2VA。

安装方式:面板嵌入式,垂直(⊥)安装 Panel embedded, vertical (⊥) installation.

产品分类 Kind of products

型号

Type

展开角

angle

外形尺寸(mm

OutlineAXBXC

开孔尺寸

Cut-outmm

结构代码

Structure   code

外形图

Outline   drawing

接线图

Wiring   drawing

重量(Kg

Weight

F72-ZBKΩ,AH72-ZBKΩ

90°

240°

72X72X120

68+0.5X68+0.5

A/B

Figure 1/2

Figure  4

0.5/0.65

F96-ZBKΩ,AH96-ZBKΩ

96X96X102

92+0.5X92+0.5

A/B

Figure 1/2

Figure  3

0.6/0.75

规格表 Measuring range

测量范围

Measuring   range

中心值

Central   value

报警设定值

Alarm   setting value(±20%)

电压规格

Voltage   specification

备注

Note

0-200-5000KΩ

200KΩ

10KΩ

30KΩ

60KΩ

100KΩ

200KΩ

300KΩ

500KΩ

1000KΩ

DC24V(DC220V)

常规routine

0-20-500KΩ

20KΩ

1KΩ

3KΩ

6KΩ

10KΩ

20KΩ

30KΩ

50KΩ

100KΩ

DC24V

定制

custom

0-2-50KΩ

2KΩ

0.1K

0.3K

0.6K

1KΩ

2KΩ

3KΩ

5KΩ

10KΩ

DC24V

0-100-1000KΩ

100KΩ

10KΩ

30KΩ

60KΩ

100KΩ





DC24V(DC220V)

0-0.2-5MΩ

0.2MΩ

0.01M

0.03M

0.06M

0.1MΩ

0.2MΩ

0.3MΩ

0.5MΩ

1MΩ

DC24V(DC220V)


 外形图 Outline drawing

image.png

刻度盘Dial 

1.jpg

背部图/接线图 Back figure/Wiring diagram

image.png

使用说明书Directions for use 

仪表正确连接后,接通电源到额定电压,此时绿色指示灯亮,仪表即处于监测状态,指针指示值即为电网绝缘电阻值(自检档除外)。After the instrument is correctly connected, connect the power supply to the rated voltage, and the green indicator light will be on at this time, the instrument will be in the monitoring state, and the indicator value is the insulation resistance value of the power grid (excluding the self check file).

仪表在工作时报警设定开关应设置在所选定的报警值位置,具体报警值档位见背面展示图。用户有其他要求时可在订货时注明。When the instrument is working, the alarm setting switch shall be set at the selected alarm value position. See the back display diagram for the specific alarm value position. Other requirements of users can be noted when ordering.

如需判别仪表工作是否正常时可进行自检,将仪表后面开关设置在自检档位,仪表即进行自检,仪表能进行正常自检时指针应指示在10KΩ位置,同时报警红灯点亮,报警输出端有输出。自检完毕后必须将仪表恢复到正常报警档位上。If it is necessary to judge whether the instrument works normally, self inspection can be carried out. Set the switch at the back of the instrument to the self inspection gear, and the instrument will carry out self inspection. When the instrument can carry out normal self inspection, the pointer shall indicate the position of 10KΩ, and the alarm red light will be on, and the alarm output terminal has output. After the self-test, the instrument must be restored to the normal alarm gear.