返回首页

乐清市安航电器有限公司


双路交流电网绝缘监测仪

image.png

技术参数Technical parameters 

双路绝缘表可同时监测动力与照明两路交流电网中的绝缘电阻。

The two-way insulation meter can monitor the insulation resistance of the power and lighting two-way AC network at the same time.

测量中性点不接地(IT)系统。

Measuring neutral No grounding(IT) systems.

监测750V以下交流电网的绝缘电阻。

Monitoring the insulation at the AC network system below 750V.

当电网绝缘电阻低于设定值时,延时≤1秒输出一报警信号;When the power grid insulation resistance is lower than the set value, delay ≤1 second and output an alarm signal.

指示精度 Accuracy of indication:⑩.

报警精度 Accuracy of alarm:10KΩ±2KΩ;30KΩ±6KΩ;60KΩ±6KΩ;100KΩ±10KΩ;200KΩ±20KΩ;500KΩ±50KΩ;500KΩ±50KΩ;1MΩ±100KΩ;

环境温度 Ambient temperature range:-25℃ to +55℃。

外壳防护 Housing protection:IP44。

耐振动 Vibration resistance:2-100HZ≤0.7g。

耐电压 Dielectric test:AC2.6KV,50HZ,1min。

输出触点容量 Contact rating:AC250V,3A;DC28V,3A。

电源功耗 Power consumption:≤5VA。

工作电源Aux.power:1-2 AC220V,380V,440V;±20%。

安装方式:面板嵌入式,垂直(⊥)安装 Panel embedded, vertical (⊥) installation。

产品分类 Kind of products

型号

Type

展开角

angle

外形尺寸(mm

OutlineAXBXC

开孔尺寸

Cut-outmm

结构代码

Structure   code

外形图

Outline   drawing

接线图

Wiring   drawing

重量(Kg

Weight

外附变换器

converter

Q72D-MΩA

90°

72X72X80

68+0.5X68+0.5

A

Figure 1

Figure  4

0.4+0.8

AH-JDB-11Figure 2

61L14G

72X72X80

68+0.5X68+0.5

A

Figure 1

Figure  4

0.4+0.8

Q96D-MΩA

96X96X132

92+0.5X92+0.5

A

Figure 1

Figure  3

1.1

一体式

one-piece

外形图 Outline drawing

image.png

接线图Wiring diagram

image.png

使用说明书Directions for use

u  仪表正确连接后,接通电源到额定电压,此时绿色指示灯亮,仪表即处于监测状态,指针指示值即为电网绝缘电阻值(自检档除外)。After the instrument is correctly connected, connect the power supply to the rated voltage, and the green indicator light will be on at this time, the instrument will be in the monitoring state, and the indicator value is the insulation resistance value of the power grid (excluding the self check file).

u  仪表在工作时报警设定开关应设置在所选定的报警值位置,报警值有八档,分别为:0.01MΩ、0.03MΩ、0.06MΩ、0.1MΩ、0.2MΩ、0.3MΩ、0.5MΩ、1MΩWhen the instrument is working, the alarm setting switch shall be set at the selected alarm value position, and the alarm value has seven gears, respectively0.01MΩ、0.03MΩ、0.06MΩ、0.1MΩ、0.2MΩ、0.3MΩ、0.5MΩ、1MΩ

u  如需判别仪表工作是否正常时可进行自检,将仪表后面开关设置在自检档位,仪表即进行自检,仪表能进行正常自检时指针应指示在0.01MΩ位置,同时报警红灯点亮,报警输出端有输出。自检完毕后必须将仪表恢复到正常报警档位上。If it is necessary to judge whether the instrument works normally, self inspection can be carried out. Set the switch at the back of the instrument to the self inspection gear, and the instrument will carry out self inspection. When the instrument can carry out normal self inspection, the pointer shall indicate the position of 0.01MΩ, and the alarm red light will be on, and the alarm output terminal has output. After the self-test, the instrument must be restored to the normal alarm gear.

u  接岸电时,由于岸电系统为接地系统,仪表会发出误报警,此时可将开关调整到“岸电”档;仪表将指示在0.01MΩ位置,但输出常开、常闭触点不会发生转换动作,无报警输出。When connecting shore power, because the shore power system is a grounding system, the instrument will give false alarm, at this time, the switch can be adjusted to the "shore power" position; the instrument will indicate the position of 0.01MΩ, but the output normally open and normally closed contacts will not change action, and there is no alarm output.

Q72D-MΩAAH-JDB-11外附变换器亦可单独作为交流电网绝缘监测继电器使用,而不用连接指示表头(即56端子)(即56端子)。56号、78端子输出信号为0-1mA电流信号,用于驱动外接指示仪表表头;而该输出电流信号与绝缘监测仪相对应关系。Q72D-MΩAAH-JDB-11 external converter can also be used as insulation monitoring relay of AC power grid independently without connecting indicator heads (i.e. 5 and 6 terminals) (i.e. 5 and 6 terminals). The output signals of terminals 5 and 6, 7 and 8 are current signals of 0-1ma, which are used to drive the external indicator meter; and the output current signal corresponds to the insulation monitor.